Loading...

Ventilation Systems with schematic diagram





S.NO AHU No. Technical Specs Details
1 AHU1- Sampling No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
60
800
25+-2
25+-5%
EU4 (Box Type)
EU5(Flange Type)
3 TR
2 AHU2- Sampling+A/L No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
60
1600
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
4 TR
3 AHU3- Vial Decarting No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
25
1600
25+-2
NA
20
EU4 (Box Type)
EU5(Flange Type)
4 TR
4 AHU4- Corridor+Laundry Room No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
25 3000 25+-2 NA EU4 (Box Type)
EU5(Flange Type)
7.5 TR
5 AHU5- Passage+Chng Room No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
30
2000
NA
NA
EU4 (Box Type)
EU5(Flange Type) 5 TR
6 AHU6- Passage+Bunk wash No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
30
3000
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
7.5 TR
7 AHU7- Vial Washing-II No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
2000
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
5 TR
8 AHU8- Vial washing-I No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
2000
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
5 TR
9 AHU9- Vial Filling-I+ Vial Sealing-I No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
90
3400
18+-2
18+-5%
EU4 (Box Type)
EU5(Flange Type)
11 TR
10 AHU10- Vial Filling-II+ Vial Sealing-II No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
90
3400
18+-2
18+-5%
EU4 (Box Type)
EU5(Flange Type)
11 TR
11 AHU11- Passage-I+II No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
60
5500
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
11 TR
12 AHU12- A/L-5& A/L-2 No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
60
800
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
2 TR
13 AHU13- Passage+Room No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
1600
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
4 TR
14 AHU14- Dispensing-I+Mixing-I No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
90
2000
18+-2
18+-5%
EU4 (Box Type)
EU5(Flange Type)
7.5 TR
15 AHU15- Dispensing-II+Mixing-II No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
90
2000
18+-2
18+-5%
EU4 (Box Type)
EU5(Flange Type)
7.5 TR
16 AHU16- Cool Zone No. Of air changes
Air quantity
Design temperature
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
60
1600
25+-2
22+-5%
EU4 (Box Type)
EU5(Flange Type)
5.5 TR



S.NO AHU No. Technical Specs Details
1 AHU1- Dispensing No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
60
800
25+-2
40+-5%
EU4 (Box Type)
EU5(Flange Type)
3 TR
2 AHU2- Dispensing+A/L No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
60
1200
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
3 TR
3 AHU3- Granulation+Washing No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
60
6000
25+-2
40+-5%
EU4 (Box Type)
EU5(Flange Type)
16.5 TR
4 AHU4- RM Store+Wasing No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
30
5500
NA
NA
EU4 (Box Type)
EU5(Flange Type)
FDV
5 AHU5- Blending+Hold No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
1200
25+-2
40+-5%
EU4 (Box Type)
EU5(Flange Type)
4 TR
6 AHU6- Tool Room+A/L No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
2000
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
5 TR
7 AHU7- Compression-I No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
1200
25+-2
40+-5%
EU4 (Box Type)
EU5(Flange Type)
4 TR
8 AHU8-Compression-II No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
1200
25+-2
40+-5%
EU4 (Box Type)
EU5(Flange Type)
4 TR
9 AHU9-Compression-II No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
60
3000
25+-2
40+-5%
EU4 (Box Type)
EU5(Flange Type)
8.5 TR
10 AHU10-Corridor No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
25
3000
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
7.5 TR
11 AHU11-Holding+Inspection No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
800
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
2 TR
12 AHU12-Corridor+chng room No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
25
300
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
7.5 TR
13 AHU13-Day Hold+Hold No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
800
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
2 TR
14 AHU14-Day Hold+Hold No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
800
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
2 TR
15 AHU15-Capsule F/S+IPQC No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
1600
25+-2
NA
EU4 (Box Type)
EU5(Flange Type)
4 TR
16 AHU16-Blister No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
1200
25+-2
40+-5%
EU4 (Box Type)
EU5(Flange Type)
4 TR
17 AHU17-ALU ALU No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
2400
25+-2
40+-5%
EU4 (Box Type)
EU5(Flange Type)
7.5 TR
18 AHU18-Dry Mixing+Area No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
2200
25+-2
40+-5%
EU4 (Box Type)
EU5(Flange Type)
8.5 TR
19 AHU19-Dry F/S No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
1400
25+-2
40+-5%
EU4 (Box Type)
EU5(Flange Type)
5 TR



S.NO AHU No. Technical Specs Details
1 AHU1- Granulation No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
60
2500
20+-2
20+-5%
EU4 (Box Type)
EU5(Flange Type)
8.5 TR
2 AHU2- Compression No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
800
20+-2
20+-5%
EU4 (Box Type)
EU5(Flange Type)
3 TR
3 AHU3- Coating No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
2000
20+-2
20+-5%
EU4 (Box Type)
EU5(Flange Type)
7.5 TR
4 AHU4- ALU ALU No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
1200
20+-2
20+-5%
EU4 (Box Type)
EU5(Flange Type)
4 TR
5 AHU5- Day Mixing+FS No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
2700
20+-2
20+-5%
EU4 (Box Type)
EU5(Flange Type)
8.5 TR
6 AHU6- Corridor+IPQC+Hold No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
30
1600
20+-2
20+-5%
EU4 (Box Type)
EU5(Flange Type)
5.5 TR
7 AHU7- Media Prep.+AutoClave No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
1200
20+-2
NA
EU4 (Box Type)
EU5(Flange Type)
3 TR
8 AHU8- SLT+COOL ZONE No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
1400
20+-2
NA
EU4 (Box Type)
EU5(Flange Type)
4 TR
9 AHU9- MLT ROOM+A/L No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
800
20+-2
NA
EU4 (Box Type)
EU5(Flange Type)
2 TR
10 AHU10- A/L No. Of air changes
Air quantity (cfm)
Design temperature (deg C)
Relative Humidity
Pre-Filter
Fine filter section
Cooling coil/AC unit
40
800
20+-2
NA
EU4 (Box Type)
EU5(Flange Type)
3 TR



Scroll to Top