HVAC system at Maxmed Lifesciences:
The Air Handling Systems (AHUs) at Maxmed Lifesciences (P) Ltd. designed to supply clean and conditioned air of specified quality to the destination places. The systems consist of units and associated devices like Supply/Exhaust Blowers, Cooling Coils, Strip Heaters, Supply and return Duct Dampers, filters and insulators as per the clean air requirements. The AHU systems are designed to meet the ISO 14664-1 specifications.
There are a total of 45 AHUs in the facility spread over three floors.
S.NO | AHU No. | Technical Specs | Details |
1 | AHU1- Sampling | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
60 800 25+-2 25+-5% EU4 (Box Type) EU5(Flange Type) 3 TR |
2 | AHU2- Sampling+A/L | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
60 1600 25+-2 NA EU4 (Box Type) EU5(Flange Type) 4 TR |
3 | AHU3- Vial Decarting | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
25 1600 25+-2 NA 20 EU4 (Box Type) EU5(Flange Type) 4 TR |
4 | AHU4- Corridor+Laundry Room | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
25 3000 25+-2 NA EU4 (Box Type) EU5(Flange Type) 7.5 TR |
5 | AHU5- Passage+Chng Room | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
30 2000 NA NA EU4 (Box Type) EU5(Flange Type) 5 TR |
6 | AHU6- Passage+Bunk wash | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
30 3000 25+-2 NA EU4 (Box Type) EU5(Flange Type) 7.5 TR |
7 | AHU7- Vial Washing-II | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 2000 25+-2 NA EU4 (Box Type) EU5(Flange Type) 5 TR |
8 | AHU8- Vial washing-I | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 2000 25+-2 NA EU4 (Box Type) EU5(Flange Type) 5 TR |
9 | AHU9- Vial Filling-I+ Vial Sealing-I | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
90 3400 18+-2 18+-5% EU4 (Box Type) EU5(Flange Type) 11 TR |
10 | AHU10- Vial Filling-II+ Vial Sealing-II | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
90 3400 18+-2 18+-5% EU4 (Box Type) EU5(Flange Type) 11 TR |
11 | AHU11- Passage-I+II | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
60 5500 25+-2 NA EU4 (Box Type) EU5(Flange Type) 11 TR |
12 | AHU12- A/L-5& A/L-2 | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
60 800 25+-2 NA EU4 (Box Type) EU5(Flange Type) 2 TR |
13 | AHU13- Passage+Room | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 1600 25+-2 NA EU4 (Box Type) EU5(Flange Type) 4 TR |
14 | AHU14- Dispensing-I+Mixing-I | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
90 2000 18+-2 18+-5% EU4 (Box Type) EU5(Flange Type) 7.5 TR |
15 | AHU15- Dispensing-II+Mixing-II | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
90 2000 18+-2 18+-5% EU4 (Box Type) EU5(Flange Type) 7.5 TR |
16 | AHU16- Cool Zone | No. Of air changes Air quantity Design temperature Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
60 1600 25+-2 22+-5% EU4 (Box Type) EU5(Flange Type) 5.5 TR |
S.NO | AHU No. | Technical Specs | Details |
1 | AHU1- Dispensing | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
60 800 25+-2 40+-5% EU4 (Box Type) EU5(Flange Type) 3 TR |
2 | AHU2- Dispensing+A/L | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
60 1200 25+-2 NA EU4 (Box Type) EU5(Flange Type) 3 TR |
3 | AHU3- Granulation+Washing | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
60 6000 25+-2 40+-5% EU4 (Box Type) EU5(Flange Type) 16.5 TR |
4 | AHU4- RM Store+Wasing | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
30 5500 NA NA EU4 (Box Type) EU5(Flange Type) FDV |
5 | AHU5- Blending+Hold | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 1200 25+-2 40+-5% EU4 (Box Type) EU5(Flange Type) 4 TR |
6 | AHU6- Tool Room+A/L | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 2000 25+-2 NA EU4 (Box Type) EU5(Flange Type) 5 TR |
7 | AHU7- Compression-I | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 1200 25+-2 40+-5% EU4 (Box Type) EU5(Flange Type) 4 TR |
8 | AHU8-Compression-II | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 1200 25+-2 40+-5% EU4 (Box Type) EU5(Flange Type) 4 TR |
9 | AHU9-Compression-II | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
60 3000 25+-2 40+-5% EU4 (Box Type) EU5(Flange Type) 8.5 TR |
10 | AHU10-Corridor | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
25 3000 25+-2 NA EU4 (Box Type) EU5(Flange Type) 7.5 TR |
11 | AHU11-Holding+Inspection | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 800 25+-2 NA EU4 (Box Type) EU5(Flange Type) 2 TR |
12 | AHU12-Corridor+chng room | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
25 300 25+-2 NA EU4 (Box Type) EU5(Flange Type) 7.5 TR |
13 | AHU13-Day Hold+Hold | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 800 25+-2 NA EU4 (Box Type) EU5(Flange Type) 2 TR |
14 | AHU14-Day Hold+Hold | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 800 25+-2 NA EU4 (Box Type) EU5(Flange Type) 2 TR |
15 | AHU15-Capsule F/S+IPQC | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 1600 25+-2 NA EU4 (Box Type) EU5(Flange Type) 4 TR |
16 | AHU16-Blister | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 1200 25+-2 40+-5% EU4 (Box Type) EU5(Flange Type) 4 TR |
17 | AHU17-ALU ALU | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 2400 25+-2 40+-5% EU4 (Box Type) EU5(Flange Type) 7.5 TR |
18 | AHU18-Dry Mixing+Area | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 2200 25+-2 40+-5% EU4 (Box Type) EU5(Flange Type) 8.5 TR |
19 | AHU19-Dry F/S | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 1400 25+-2 40+-5% EU4 (Box Type) EU5(Flange Type) 5 TR |
S.NO | AHU No. | Technical Specs | Details |
1 | AHU1- Granulation | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
60 2500 20+-2 20+-5% EU4 (Box Type) EU5(Flange Type) 8.5 TR |
2 | AHU2- Compression | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 800 20+-2 20+-5% EU4 (Box Type) EU5(Flange Type) 3 TR |
3 | AHU3- Coating | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 2000 20+-2 20+-5% EU4 (Box Type) EU5(Flange Type) 7.5 TR |
4 | AHU4- ALU ALU | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 1200 20+-2 20+-5% EU4 (Box Type) EU5(Flange Type) 4 TR |
5 | AHU5- Day Mixing+FS | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 2700 20+-2 20+-5% EU4 (Box Type) EU5(Flange Type) 8.5 TR |
6 | AHU6- Corridor+IPQC+Hold | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
30 1600 20+-2 20+-5% EU4 (Box Type) EU5(Flange Type) 5.5 TR |
7 | AHU7- Media Prep.+AutoClave | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 1200 20+-2 NA EU4 (Box Type) EU5(Flange Type) 3 TR |
8 | AHU8- SLT+COOL ZONE | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 1400 20+-2 NA EU4 (Box Type) EU5(Flange Type) 4 TR |
9 | AHU9- MLT ROOM+A/L | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 800 20+-2 NA EU4 (Box Type) EU5(Flange Type) 2 TR |
10 | AHU10- A/L | No. Of air changes Air quantity (cfm) Design temperature (deg C) Relative Humidity Pre-Filter Fine filter section Cooling coil/AC unit |
40 800 20+-2 NA EU4 (Box Type) EU5(Flange Type) 3 TR |